300A Battery Through-Wall Terminal Pair, M8 Busbar Tab, Covered Panel Mount

300A Battery Through-Wall Terminal Pair, M8 Busbar Tab, Covered Panel Mount

Available to order Ships in 4–6 weeks.

Regular price $73.00 CAD
Regular price Sale price $73.00 CAD
Sale Sold out
Quantity
  • Ships from Michigan

Take the main current out of a battery box without a cable gland.

Sold as a pair: one black terminal for negative and one orange for positive. A copper bar runs through a square insulated body that screws into the enclosure wall. Inside, your busbar or ring lug bolts to an M8 threaded tab. Outside, the cable lug bolts to the terminal under a hinged snap cover.

At a Glance

  • 300A rated, up to 1500V DC. Nickel-plated copper conductor, one piece from inside to outside.
  • M8 threaded tab inside the box. Flexible busbar, BMS bar or ring lug bolts flat onto a 25 mm copper tab.
  • Covered terminal outside. A hinged snap cover closes over the cable lug so the live terminal isn't exposed.
  • Simple panel mount. 50 x 50 mm flange, four M4 screws on a 38 x 38 mm square.
  • Sold as a pair. One black (negative) and one orange (positive), so polarity is clear at a glance.

What You Need With It

Installing It

  • Cut the panel opening and drill four 4.3 mm holes on a 38 x 38 mm square using the mounting drawing in the photos.
  • Fit the terminal from the outside and fasten it with the four M4 screws and nuts included.
  • Inside, bolt your bar or lug flat onto the tab with an M8 bolt. The thread is 7 mm deep, so check the bolt length clamps the bar before it bottoms out.
  • Support the bar or cable so it doesn't lever on the tab, then close the outside cover.

Through-Wall Terminal or Quick Disconnect?

A through-wall terminal is a fixed, bolted connection: low resistance, nothing to unplug, and the cheapest way to get high current through a box wall. If you need to unplug the battery often, use the 250A quick disconnect pair instead.

Size the whole chain, not just the terminal. The fuse protects the cable and this terminal, so both must carry the fuse rating. A 300A terminal does not make 1 AWG cable a 300A cable.

Pair Includes

  • 2 through-wall terminals (1 black, 1 orange), each with a hinged snap cover
  • 8 M4 screws and nuts (4 per terminal)
  • 2 M8 bolts

Technical Specifications

  • Rated current: 300A
  • Rated voltage: up to 1500V DC
  • Conductor: copper, nickel plated
  • Housing: PBT
  • Inside terminal: 25 mm copper tab, M8 internal thread, 7 mm usable depth, 41.7 mm from the flange
  • Outside terminal: bolted, under a hinged snap cover
  • Flange: 50 x 50 mm, about 33 mm deep
  • Mounting: 4 x M4 screws on a 38 x 38 mm square (4.3 mm holes)
  • Rated cycles: 1000
  • Colors: one black, one orange per pair

Questions

What's in the pair?
One black terminal for negative and one orange for positive, which is what one battery needs. Each comes with its hinged cover, four M4 screws and nuts, and an M8 bolt.

What cable size does 300A need?
Size the cable to your fuse, not to this terminal. A 200A BMS pack takes a 250A Class T fuse and 2/0 AWG cable. For anything larger, check your cable's rated ampacity at the temperature inside your box. The outside terminal takes a ring lug on the M8 bolt.

How does it attach inside the box?
Bolt a flexible busbar, BMS output bar or ring lug flat onto the 25 mm copper tab with an M8 bolt. The thread is 7 mm deep, so use a bolt that clamps the bar before it bottoms out.

Is it waterproof?
No IP rating is published. The cover protects the outside terminal from touch, not water. Mount it where it stays dry, or seal the flange to the panel.

Can I disconnect the battery with it?
Only by unbolting the cable with the system off. For a plug-and-unplug connection, use the 250A quick disconnect pair.

Before you check out

This terminal pair • Class T fuse • flexible busbar • lug crimper