Battery cable size calculator
Enter your current, the length of the run and your system voltage. Your cable has to pass two checks: voltage drop (is it thick enough for the length?) and heat (can it carry the fuse rating without overheating?). Whichever check needs the bigger cable sets your size.
Next steps
All sizes for your run
| Size | mm² | Carries | Drop at your current |
|---|
"Carries" is the allowable current for your insulation rating, bundling and hot space. Copper, stranded.
How we work this out
Voltage drop. The cable's resistance turns some of your voltage into heat. We find the smallest size whose cross-section (in circular mils) is at least 10.75 × current × round-trip feet ÷ allowed drop in volts. 10.75 is the resistance of copper per circular mil-foot, the same basis as the common marine wire charts.
Heat. The allowable current for each size comes from the US Coast Guard conductor table (33 CFR 183.425, Table 5): stranded copper in free air at 30 °C, by insulation rating. We reduce it for bundling (×0.70 for 3 cables, ×0.60 for 4 to 6, ×0.50 for 7 or more) and for a hot space (×0.85 at 105 °C down to ×0.58 at 60 °C), as the table's notes say. The result must be at least your fuse rating, so the fuse protects the cable.
Your size. The cable has to pass both checks, so the larger of the two sizes is your minimum. Going one size up costs a little more and runs cooler.
Cable size chart
Each block is the minimum size that passes both checks, with the fuse at 125 % of the current. Your numbers are outlined. Change the voltage, drop, insulation or bundling above and the chart follows.
Disclaimer: For reference only. Do proper engineering to determine your requirements and always follow applicable code (NEC, ABYC or your local code).
Assumes copper cable and clean, properly crimped and torqued lugs.